MV-DS Medium Voltage, Digital Soft Starter 2,300-15,000V, 60-1,200A (Busbar Version)
Full Featured, Microprocessor-Based, for Motors 60-1,200A, 200-26,150KW, 2300-15,000V.
The MV-DS is a third generation, Medium Voltage, digital soft starter, designed for use with standard asynchronous and synchronous motors. This highly sophisticated soft starter ensures smooth, step-less acceleration and deceleration, eliminating current and mechanical shocks on motor and load.
The MV-DS may be supplied as chassis type or a complete system including Line and/or Bypass Contactors. Addible options are Load Break Switch, Fuses, Motor Protection Relay, etc.
Advantages at a Glance
- Innovative low voltage test mode - full testing with a small L.V motor using standard built in features
- Advanced Electronic Potential Transformer utilizing Patent Pending "wireless" fiber-optic firing system
- Each starter is tested for Partial Discharge (Korona) ensuring long term reliability
- Power factor capacitors can be connected directly to the upstream contactor
- Heavy duty design at 50°C ambient temperature
- Reduced inrush current and mechanical shock
- Third generation microprocessor circuitry
- Soft, step less acceleration & deceleration
- Unique starting & stopping characteristics
- Sophisticated motor protection package
- User friendly, easy setting and operation
- IP30-standard, higher protection by special order
- Two optional methods of delivery: Chassis type for self assembly or Complete system
- RS485 Communication with MODBUS, PROFIBUS or MODBUS/TCP protocols (others - upon request)
- Wide 45-65Hz Auto-tracking frequency range combining special software with unique hardware arrangement (designed for Marine, Offshore and Generators operating under continuous frequency variation)
- Torque and current starting and stopping characteristics
- Pump control software
Starting & Stopping
- Illuminated LCD with 2 lines, 16 characters each
- Selectable languages: English, German, French or Spanish
- The LCD displays motor current, fault description and statistical data
- Easy setting using six soft-touch keys with default parameters
- Eight LEDs for a quick status display
- Control voltage On-Self Test OK
- Motor soft starting
- Motor running
- Motor soft stopping
- Motor stopped
- Test Mode Activated
- Dual Adjust mode
- Fault
Statistics
- Last Starting Period
- Last Start Maximum Current
- Total Run Time
- Number of Starts
- Last Trip
- Trip Current
- Total Number of Trips
- Historical Trip Event Recorder (10 Event conditions)
Control Inputs & Outputs
- Control voltage: 110-120, 220-240VAC / 50-60Hz or 110 - 220VDC to be specified
- Separate inputs for Start, Stop (Emergency) and Soft Stop
- Two programmable External fault inputs - will stop the motor 2 sec. After the contact closes
- Aux. Contacts - three C/O relays, 8A, 250V, 2000VA
- Immediate Relay - changes position upon start signal, with adjustable On & Off delays
- Returns to original position upon Voltage Outage, Fault, Stop signal and Soft stop signal at the end of soft stopping process. It can also be configured as a "Shear-pin Alarm" contact.
- End of Acceleration Relay - operates upon completion of starting process, with adjustable On delay. Returns to original position upon Voltage outage, Fault, Stop and Soft Stop signals.
- Fault Relay - can be programmed as:
- Fault - changes position upon Fault, returns to original position upon Reset.
- Fault-Fail-Safe - changes position upon control voltage connection, returns upon fault.
Typical Applications
- Fans and centrifuges
- Conveyors and monorail systems
- Pumps, Compressors and Chillers
- Starting large motors from weak power supply (diesel generators, long supply lines, etc.)
Marine & Offshore Applications
- Thrusters
- Cargo Pumps (LNG, LPG, etc.)
- Water & Ballast pumps
- Refrigeration compressors
- Hydraulic pumps & power packs
- Main Propulsion (Variable Pitch Propellers)